Water is disinfected but never completely sterilized in the
water treatment process. This disinfection is a two part process that includes:
Contact time and kinetics are simply a measure of the inactivation due to time and concentration of the disinfectant. The USEPA has developed regulations for the minimum kill percentages (inactivation) necessary for public water to be considered potable. These regulations include a minimum disinfection of:
Varying degrees of disinfection can be attained by altering the type and concentration of disinfectant, as well as the time water is in contact with the disinfectant. The decision to use one type of disinfectant versus another will set the precedence for the remainder of the values needed to attain the proper disinfection. The time untreated water is exposed to the disinfectant and the concentration of that disinfectant are the main factors in the equation that will be discussed in the next section. (Notice that the units of contact time are (mg/l)(min).)
A relationship between kill efficiency and contact time, was developed by Harriet Chick while she was a Fellow in the Pasteur institute in Paris, France. The research yielded data supporting her relationship that is shown in Figure 2 below. (No) represents the initial number of organisms and N is the number of organisms at time t. As contact time between water and disinfectant increases, the ratio of No/N decreases as Chick's Law predicts.

Watson later modified Chick's equation to account for varying types of disinfectants. He developed coefficients that better represented the strength of the disinfectant as well as the pH of the water. From this research, the coefficient of specific lethality (lambda) was developed. Watson’s modification of Chick’s equation is shown below.
Table 1: C*t for Removal of Giardia Cysts in Relation to Log Removal and pH
| Log Removal | pH <6 | pH 6.5 | pH 7.0 | pH 7.5 |
|---|---|---|---|---|
| 1.0 | 46 | 54 | 65 | 79 |
| 1.5 | 69 | 82 | 98 | 119 |
| 2.0 | 91 | 109 | 130 | 158 |
| 2.5 | 114 | 136 | 163 | 198 |
Table 2: C*t Values for the 99% Inactivation at 5 Degrees Celsius of Organisms Using Various Disinfectants
| Organism | Free Chlorine (pH 6-7) | Chlorine Dioxide (pH 6-7) | Ozone (pH 6-7) |
|---|---|---|---|
| E.Coli | 0.034-0.05 | 0.4-0.75 | 0.02 |
| Rotavirus | 0.01-0.05 | 0.2-2.1 | 0.006-0.06 |
| Giardia lamblia cysts | 47-150 | - | 0.5-0.6 |
| Crytosporidium parvum | 7200* | 79* | 5-10* |
* 99% inactivation at 25 degrees C
Contact time and credit are essential in the design of a water treatment plant. In addition to the Environmental Protection Agency, the Virginia Department of Health regulates these values. Regulations governing credit have been discussed above, but contact time is dependent upon the specific plant. Most plants attain the required C*T in the clearwell, and the Blacksburg Water Authority (BAT) is no exception.
Since its creation in 1950, the water demand in the area has risen sharply. The BAT has been forced to convert all available space to expand the size of the c learwell. The result is a poorly baffled clearwell that does not retain the water long enough to get the credit it needs to meet regulations.
The following calculations are not entirely relevant to this topic, but the result is. They are taken from actual calculations by Jennifer Barber for the Blacksburg Water Authority in 1991. Before beginning the calculations, two terms must be defined. T-theo is the time one drop of water spends in the clearwell, theoretically. Baffling factor, BF, is a term that accounts for the mixing that occurs in the clearwell. Short-circuiting can be avoided by proper baffling. Below is a table of BF values.
Table 3: Baffling Factor Values
| Baffling Condition | BF | Baffling Description |
|---|---|---|
| Unbaffled (Mixed Flow) | 0.1 | No baffling; very low length to width ratio |
| Poor | 0.3 | Single or multiple unbaffled inlets and outlets; no intrabasin baffles |
| Average | 0.5 | Baffled inlet or outlet with some intrabasin baffles |
| Superior | 0.7 | Perforated inlet baffle, serpentine, end-around, or perforated intrabasin baffles |
The Blacksburg Water Authority attains credit for disinfection in the clearwell. The volume of the clearwell is 162,760 gallons, and the flow out of the clearwell is 12.4 MGD.
T-theo = (162,760 gal) / [ 12.4 MGD*694.4 GPM/MGD ] = 18.9 minFigure 4: Blacksburg Water Authority Caustic Addition System
The most likely solution, though, will involve the construction of an on-site storage facility. This will increase the time water is in contact with the chlorine, thus increasing the log inactivation and credit for disinfection.
We would like to thank those who made this project possible. Dr. Hoehn and
Dr. Gallagher of Virginia Tech provided us with technical information and
computer assistance. Jerry Higgins of the Blacksburg Water Authority took
the time to show us how this topic applied to his water treatment plant.
For more information regarding Blacksburg's water supply, visit their web site at